Handover audit findings

What our engineers found at various handovers

Lifts, fire-fighting, sewage treatment plants and diesel generators: four reports counted from our engineers’ own written observations, from the handover audits residents’ associations have commissioned from us since 2017. No building, builder or association is named.

The four reports

Four systems residents assume are ready on day one

Each report is four pages: the headline numbers, the patterns behind them, the checks that failed most often, and how the counting was done.

Lifts

Lift safety and function

12in-depth lift audits
1,283of 3,543 checks failed
347rated high priority

Worst failure rateA statutory operating licence, displayed where residents can see it: failed 69 of 115 times.

  • Earthing and wiring was the largest pattern (272 findings).
  • An intercom that lets someone shut in the car reach a person failed 28 of 68 times.
As reported in The Times of India

Fire-fighting

Sprinklers, hydrants, alarms and extinguishers

43handovers covered
25,732failures recorded
9,718rated high priority

Most widespreadNo fire extinguisher where one was required: found in 33 of 43 projects.

  • Protective caps still on sprinkler heads in 28 of 43 projects.
  • No key or means of opening a hose cabinet or fire-shaft door in 22 of 43.

Sewage treatment plant

The STP, its pumps and its operators

34handovers covered
325 of 677checklist questions failed
596rated high priority

Most seriousRaw sewage or sludge sent out of the premises without treatment: recorded in 9 projects.

  • Plant run in manual, not automatic, mode in 14 of 18 projects asked.
  • No first-aid kit inside the plant in 19 of 22 projects asked.

Diesel generator (DG) set

The DG set, its fuel and its wiring

37handovers covered
1,028failures recorded
396rated high priority

Most widespreadEarthing not done, not connected or not done properly: found in 31 of 37 projects.

  • Oil, diesel or fuel leaking or spilt in 25 of 37 projects.
  • Statutory approvals not produced or not on display in 6 of 12 projects asked.

A common thread

Earthing came up in three of the four

IS 3043 is the Indian Standard code of practice for earthing, and it comes up in all three of these reports.

Lifts272

findings on earthing and wiring, the largest lift pattern, in 10 of 12 projects

STP23 of 34

projects with earthing missing, not connected or not done to IS 3043

DG set31 of 37

projects with earthing not done, not connected or not done properly

How to read these numbers

What the reports do not say

Found so they would be fixed

A handover audit gives the association a list to hand back to the builder before it accepts the building. Nothing here is the current condition of any building.

No one is named

No building, builder or residents’ association is identified, in the reports or on this page.

Not a random sample

Every project here had an association organised enough to commission an independent audit, which may make it better managed than average, not worse.

Counts, not estimates

Every figure is a count of records written down on site. Severity is the engineer’s call on site. Each report sets out exactly how it counted.